SG Three-phase Dry-type Power Transformer
SG Three-phase Dry-type Power Transformer
power Transformer component | Temperature rise limit K | Measuring method | Items | Allowable degree of deviation (%) | ||
Coil | B | 80 | No-load loss | +15 | ||
F | 100 | Load loss | +15 | |||
Iron core and surface of the structural components | The max. value shall not exceed the allowable temperature rise limit of the contact insulation material | thermometry or thermocouple method | Total loss | +10 | ||
Insulation level:The transformer withstands 2000V power frequency testing voltage without breakdown or flashover in 1 minuteAt frequency and voltage multiplying in 1 minute. The performance of transformer shall not exceed the allowable deviation value in the following table. | No-load current | +30 | ||||
Impedance voltage | ±10 | |||||
Transformer ratio | ±0.5 | |||||
DC resistance unbalanced ratio | Iine | 2 | ||||
Phase | 4 | |||||
Remarks: If the DC resistance unbalanced ratio of three-phase transformer exceeds the specified range in Form 2 due by the reason of material of coil and structure, the measured value shall be recorded in the delivery test record and the very reasons also be noted. |
SG Three-phase Dry-type Power Transformer